Product Description
LynTec SGX20-4 Power Conditioning Surge Suppressor with 4 Module Units
Overview
The SGX20 shall be housed in a steel enclosure. It shall operate from 120 volts AC and have a barrier strip accessible through knock-outs in the enclosure for hardwiring power input and output connections.
The SGX20 shall have a load rating of 20 amps per circuit at 120 volts, a self-test circuit with visual indicator and provide EMI/RFI filtering. It shall meet Federal Grade A, Class 1, Mode 1 guidelines for powerline surge suppressors and withstand at least 1000 occurrences of surge pulse voltages up to 6000 volts.
Features
- Factory installed in LynTec sidecars and ships attached to Lyntec panels
- Advanced series mode surge protection
- Advanced impedance tolerant EMI/RFI filtering
- Self-test circuit with visual indicator
- 10-year warranty
Specifications
- UL Rated - Yes
- Warranty - Yes
- Spec Sheet available - Yes
- Spec Sheet available - Yes
- Operating Temperature (Maximum): 95 F
- Operating Temperature (Minimum): 41 F
- Certifications: UL, ETL, CSA
- Current Rating: 20 Amps
- UL Rated: Yes
- Warranty (Length/Type): 10 Years Limited
- Load Rating: 20 amps per circuit at 120 volts
- Power Requirement (no load): 15 watts per circuit
- Surge Let-Through Voltage (6000-volt surge): 0 V
- UL 1449 Adjunct Classification Test Results: 1000 surges, 6000 volts, 3000 amps, B3 pulse
- Measured suppressed voltage: 170 volts; no failures
- Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
- EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB at 100 kHz; 50 dB at 300 kHz; 50 dB at 3 MHz; 50 dB at 30 MHzEMI/RFI Filter, Common Mode (50-ohm load):18 dB at 300 kHz; 30 dB at 1 MHz; 50 dB at 5 MHz; 50 dB at 20 MHz
- Maximum Applied Surge Voltage: 6000 V
- Maximum Applied Surge Current: Unlimited, due to current limiting
- Maximum Applied Surge Energy: Unlimited, due to current limiting
- Endurance (C62.41-1991 category B3 pulses): 1 kV>500,000; 3 kV>10,000; 6 kV>1000
- Humidity Range: 5 to 95 % R.H ( Non-condensing)