Product Description
Hubbell WSP-LWO-EM-UNV Wet Location Occupancy Sensor - PIR - End Mount - 120V/277V
Wet Location Occupancy Sensor - PIR - End Mount - 120V/277V - White |
WASP Occupancy Sensor
Features
- Digital Passive Infrared (PIR) sensor
- Multiple (single and dual) output versions
- Unique Smart Cycling for improved lamp life
- End mount and surface mount versions
- Interchangeable high/low area detection lens options (sold separately)
- Low voltage and line voltage models available
- Daylight sensor for daylight harvesting applications
- Low temperature/water-tight/indoor-outdoor versions
Specs
Construction
- Sensor module and lens assembly - high impact, injection-molded plastic
- 4.0" x 1.5" H (101.6mm x 38.1mm H)
- 7.0 oz. (198.45g)
- White, Black and Gray
- (1) 12-pin dip switch
- Dual element pyrometer and spherical Fresnel lens designed for robust detection of a walking person
- Lens Options
- Low Mount/High Mount:
- Indoor/Outdoor
- Coverage: 360°, 180°, Aisle, Half Aisle
- Lenses sold separately
Mounting
- End mount sensor: Mounts directly to end of fixture through extended 1/2": (12.7mm) chase nipple
- For deeper body fixtures, an optional Extender Adapter (available separately) positions the sensor flush or below the bottom of the reflector for a full field-of-view
- Surface mount sensor: Mounts directly to fixture or j-box via (2) 1.25" (31.75mm) stainless steel screws and locking nuts
Electrical
- Line Voltage sensors: 120/277/347VAC, 208/240VAC, 480VAC, 60 Hz
- Low Voltage sensors: 24VDC (uses UVPP or MP-Series power pack – not included)
- 120VAC: 0-800W ballast or 0-600W tungsten, 60Hz
- 277VAC: 0-1200W ballast
- 347VAC: 0-1500W ballast
- 208/240VAC: 0-1200W ballast
- 480VAC: 0-2400W ballast
- ¼ HP motor load @ 120VAC, 1/6HP @ 347VAC
- 24VDC active high-logic control signal
- Relay: N/O + N/C contacts; 500mA rated @ 24VDC; three wire isolated relay
Operation
- Coverage: 360°, 180°, Aisle, Half Aisle
- Timer Settings
- Primary: 8-second test mode - 4, 8, 16 and 30 minute timeouts
- Secondary: can be disable (switches off with primary timer) - 30, 60 and 90 minute timeouts
- Daylight Sensor
- Range: 30 - 2500fc
- End mount sensor: Downward and upward looking daylight sensors (Direction selectable via dip switch)
- Surface mount sensor: Downward looking daylight sensor only
Operating Environment
- Operating temperature: 32° to 149°F (0° to 65°C)
- Relative humidity (non-condensing): 0% to 95%
- Low-temperature/WaterTight/Indoor-Outdoor version: Operating temperature: -40° to 149°F (-40° to 65°C)
Ordering Information