Product Description
ILC RRU-UNV Shunt Relay for Line Voltage and DALI Applications
The RRU-UNV includes a 20A rated high voltage Form C (N/O+N/C) relay and is UL924 Listed for emergency lighting control applications. The RRU-UNV can bypass a line voltage switch or dimmer, ensuring that an emergency fixture illuminates at full brightness during a utility power interruption. It can also be used to open or short a DALI control signal. Its small size makes it ideal for junction box mounting in wireless or other modern lighting control systems. An integral test switch and LED allow for quick testing and verification of proper function.
Features
- Integral test switch and green utility power indicator
- UL924 Listed
- Can be used to bypass both traditional and self-powered DALI systems
- 20A Rated N/O & N/C - Used for bypassing line voltage switching, occupancy sensors or dimmers. Also used as dry contact to signal relay panels or BMS systems or utility power interruption
Specs
- Sensing Input
- 120V-277V
- LED Load Rating
- 120V-277V (20A)
- Ballast Load Rating
- 20A (120-277V)
- Incandescent Load
- 1200W (120V) / 1500W (277V)
- Mounting
- Universal (flush, panel, fixture or junction box mount)
- Rating
- UL94-0A, Plenum Rated, Damp Location Related
- Shipping Weight/Color
- 12.0 oz. / White
- Temperature
- 32°F - 140°F (0°C - 60°C)
- Body Size
- 1.7" x 3" x 1.2" (W x H x D body)