Product Description
ILC LSPSC-IND-P LightSync Photo Sensor Controller with Indoor Sensor - Panel Mount
The LightSync Photo Sensor monitors light levels and transmits data across the LightSync network to the lighting control panels. Each sensor has 8 individual set points for on or off control with a selectable dead-band and is programmable to control any or all relays, groups, or presets. Each sensor has a built-in adjustable filter to eliminate false triggering from lightning or other light sources. This sensor can be used for daylight harvesting to shed lighting loads or used with a dimming module to dim loads. The indoor and outdoor photocell heads convert the analog light levels to a digital form and are UV and weather resistant.
FEATURES
- Made in the USA
- Digital CAT 5 ready
- Light levels monitored indoors or outdoors to 1800 foot candles
- Control points consist of 8 individual On and Off inputs • Dead-band for each control point
- Analog to digital photocell heads
- Photocell filter to eliminate false triggering of loads
- Digitally addressable device for a unique address
- Mounting options for in the panel or at a remote location
- UV resistant photocell heads
- Encased photocell head protects sensor from the elements • Connectors are push-to-connect
SPECS
Controller Physical:
-
2.75" Wide x 3.50" High
-
Digital addressing switches
-
Power out and digital input connections
-
Remote mount has RJ45 connectors easy data line connections
-
Remote mount provided with a 4.69" x 2.25" deep steel box with cover
-
Panel mount supplied with connector for direct connection onto a relay driver board
-
Push-to-connect photo sensor input
Electrical:
- Powered from the panel or the LightSync network
Photocell Heads:
- Outdoor photocell mounts in a 1/2” LB type fitting or junction box
- Indoor photocell mounts to ceiling tile or other structure
- Indoor 45 degree photocell mounts to ceiling or other structure. Angled for light harvesting.
Controller Operating Environment:
- Location: Interior Space
- Operating Temp.: 0° to 50° C
- Humidity: 10% to 90% Non-condensing • Atmosphere: Non-explosive/corrosive
- Vibration: Stationary
Photocell Operating Environment:
- Location: Interior/Exterior Space
- Operating Temp.: -35° to 50° C
- Humidity: 10% to 100% Condensing
- Atmosphere: Non-explosive/corrosive • Vibration: Stationary
Certifications:
- UL CUL
- FCC Part 15