Product Description
ILC LSOS8I-P LightSync Occupancy Sensor 8 Input Module - Panel Mount
The LightSync Occupancy Sensor 8 Input module is designed to power and receive signals from multiple sensors on each of its 8 independent inputs. Eliminate expensive power packs by simply direct- wiring the sensors into the LightLEEDer inputs. This module mounts directly in the panel on the output module, or can be mounted remotely in a location central to the sensors. Each independent input can control any relay(s), group(s), or preset(s) throughout the network. Inputs also have a time-of-day or open/close time-of-action which could disable the input or change the relays controlled.
FEATURES
- Made in the USA
- Digital CAT-5 Ready
- Provides power and inputs for occupancy sensors
- Installs directly onto the output board
- Digitally addressable device for a unique address
- Remote mounting option for LightSync network
- RJ45 connectors for remote mounting module
- Connectors are easy non-screw push-to-connect type
- Optically isolated inputs to protect the electronics
- Sensor signals accepted directly on module
- Connect master and slave sensors to each input
- Works with most major manufactured sensors
Remote Mounting Option:
- Remote mount anywhere on the LightSync network
- Powered from a 120/277VAC power supply
- RJ45 connectors provided for easy connection
- Mounting plate available
- Great choice for centrally locating the module with sensors
SPECS
Safeguards:
- Optically isolated inputs protect electronics
Physical:
- 2.75”W x 3.5” H
- Easy non-screw push-to-connect connectors
- Digital addressing switches
- RJ45 connectors for remote mounting option
Remote Mount Physical:
- Enclosure: 6.50” x 9.25” x 2.50 ”with screw cover
- 1/2”nipple for mounting to an electrical box
- 6”wire leads provided for high voltage connection
- Push-to-connect low voltage connections
- Provided with pre-drilled mounting holes
Electrical:
- Electronics powered from LightSync data line
- Sensors powered from 120/277VAC power supply
- Current: 800mA
- Voltage: 24VDC
- Current limited circuit
Operating Environment:
- Location: Interior space
- Operating Temp.: 0° to 50° C
- Humidity: 10% - 90% Non-condensing
- Atmosphere: Non-explosive/corrosive
- Vibration: Stationary
Certifications and Approvals:
- FCC Part 15
- UL