Product Description
ILC LightLEEDer Serial Interface Network Gateway BACnet IP (LLSI-NG-BACIP)
The LightLEEDer Serial Interface Module can be added to any panel to provide control from any building automation system using BACnet IP, BACnet MSTP, Modbus RTU, Modbus ASCII, Modbus TCP, Metasys N2, or ILC serial protocol. With the panel module, commands can be sent to the panel to force relays ON and OFF, force relays On and OFF with a timer option (blink, double blink, HID delay, Alarm ON, Alarm OFF, Pulse ON, and Pulse OFF), monitor relay status, monitor input status, and enable/disable inputs. A single point gateway is available for control and status of relays, groups, and presets on the network.
Features
- Made in the USA
- Direct communications for BAS control of lighting panel
- Direct control of any relay output giving complete control
- True status of relays in the lighting panel
- Timer option commands available for blink alerts and alarms
- Allows enable/disable commands for switch inputs
- Installs directly into any panel
- Extractable files from BACnet and LonWorks modules Protocals
- BACnet IP– an ASHRAE protocol communicating on a TCP/IP network
- BACnet MSTP– an ASHRAE protocol communicating on a RS485 network
- Modbus RTU– a Modicon protocol communicating on RS485/RS232 in a binary coded format
- Modbus ASCII– a Modicon protocol communicating on RS485/RS232 in an ASCII coded format
- Modbus TCP– a Modicon protocol communicating on a TCP/IP network
- Metasys N2– a Johnson Controls protocol communicating on RS485
- ILC Open Protocol– an ILC protocol communicating on RS485/RS232 in an ASCII coded format
Warranty
- Six year limited warranty
Ordering
SERIES | MOUNT | PROTOCOL |
LLSI - LightLEEDer Serial Interface Module | Panel Level (PL) | BACnet IP = BACIP |
Gateway (NG) | BACnet MSTP= BACMSTP | |
Modbus = MOD | ||
Modbus TCP = MODTCP | ||
Metasys N2 = N2 | ||
ILC Open = ILC |
Specifications:
- Physical: • Dimensions: 2”Wide X 3”High • RJ45 connectors for Ethernet based communications • Removable screw connectors for data line communications
- Electrical: • Powered from the panel
- Operating Environment: • Location: Interiorspace • Operating Temp.: 0° to 50° C • Humidity: 10% - 90% Non-condensing • Atmosphere: Non-explosive/corrosive • Vibration: Stationary
- Certifications and Approvals: • FCC Part 15
NOTE: Physical appearance may vary between protocols.