Product Description
ILC LightMaster Panel with Slave Processor SNET version 7.23, refurbished
 
 This panel includes the following components, all of which are refurbished:
 
ILC LightMaster Slave Processor SNET version 7.23, refurbished (QTY 1)
ILC LightMaster Input/Output Card, refurbished (QTY 2)
ILC LightMaster LCD Display/Keypad, refurbished (QTY 1)
ILC LightMaster Transformer (QTY 2)
ILC 2R9C Relay 20Amp, SPST, 120/277VAC latching relay w/status (QTY 16)
The LightMaster programmable lighting control panel is suitable for all your lighting control needs. LightMaster panels range in size from 8 to 48 relays and are equipped with CAT-5 RJ-45 connectors for LightSync data line devices and interconnecting panels. Panels include a keyboard/LCD display along with RS232, RS485, or an optional TCP/IP port to enable PC control and programming. Add-on modules are available if you require connecting to BAS, theatrical, or security systems.
• Made in the USA relays and hardware. 
• Programming Options are done with an Integrated keypad with 4-line LCD display or using LightMaster Pro software via RS232 or optional TCP/IP. 
• LightSync Data Line Device Ready utilizing RJ45 connectors and standard CAT-5 cabling for data line. 
• Network capability allows you to connect panels for up to 128 panels and 254 LightSync devices on the panel network. 
• Relay Groups can consist of any relay on the network and be assigned to any of the 48 available groups —controlled by any timer, switch, or other external commands. 
• Relay Presets can be programmed from any relay On/OFF patterns and be assigned to any of the 48 available presets — controlled by any timer, switch, or other external commands. 
• Timer Scheduling for 48 available timers that can turn relays On or OFF for Time-of-Day, Astronomical times, and Open/Close. 
• Clock Functions features Automatic Astronomical calculation of Sunrise and Sunset and Adjustable Daylight Saving Time and enable/disable feature. 
• Switching Inputs accepts virtually any type of switch input, momentary or maintained, 2- or 3-wire switch. 
• Add-On Modules can be added to each controller, which include BACnet, Modbus RTU, Modbus ASCII, Metasys n2, LonWorks, DMX512, DTMF telephone switching and modem
Relays: 
• 2R9 latching relay: 120 - 277VAC @ 20 Amp for ballast and resistive loads 18,000A SCCR. 
• 2-Pole latching contactors: 208-480VAC, 20 Amps for ballast and resistive loads. 
Safeguards: 
• Power surge and spike suppression up to 123 volts on the 24VAC power input 
• Data line surge and spike suppression up to 8kv direct and 15kv through air (optional). 
• Memory retention for firmware and programming up to 10 years 
• Real-Time-Clock time retention 45 days or greater without power 
Physical: 
• Provided with pre-drilled mounting holes 
• Provided with a removable hinged locking door for flush or surface mounting 
• High voltage barriers separate normal/Emergency and Class 1/Class 2 wiring
 Electrical: 
• 120 or 277 VAC @ 1 Amp, 347 VAC optional
Capacities: 
• 1 to 48 relays 
• Contact ILC for contactor capacities 
Options: 
• Panels may be fitted with a wide variety of options such as: TCP/IP, modem, DMX 512, Metasys n2, Modbus, BACnet, LonWorks, and flush mount panel cover 
Operating Environment: 
• Location: Interiorspace 
• OperatingTemp.: 0° to 50° C 
• Humidity: 10% - 90% non-condensing 
• Atmosphere: non-explosive/corrosive 
• Vibration: Stationary 
Certifications and Approvals: 
• UL 508 
• UL 916 
• FCC Part 15 
• Title 24 
• ASHRAE compliant
 
 
             
             
             
             
             
           
           
           
           
       
                   
           
                   
           
                   
           
                   
           
                   
           
                   
           
                   
           
                  